Model 2: IDC Single Normally-Open (N.O.) Switch
In this configuration, only one normally-open dry contact closure may be installed per supervised line. In
this mode, the loop is monitored for open circuits, wire-to-wire short circuits (across + and -), and ground
faults. When the contact closure is not active (open), the loop appears as 20.1 kΩ load (15 kΩ in series
with 5.1 kΩ). This appears on the input to the MIM and indicates a healthy loop. When the contact
closure is active (closed), the 15 kΩ resistor is bypassed.
Figure 3. IDC Single Normally-Open Switch
The circuit then sees only the 5.1 kΩ load. This changes the value of the input and indicates to the MIM
that the contact closure is active. If there is a short across + and -, if either leg is grounded, or if a break
occurs on either leg, the MIM indicates that a fault has occurred.
N
OTE: The terminating resistors are not included with the MIM. These resistors are included in a kit
(12509-003) that must be ordered separately.